Your flex isn't too small. It's sagging. Weak register at the end of a flex run? Before you go up a size, look at the straps. A belly bunches the liner into folds and every fold trips the air; unsupported flex is a typical cause of excessive static pressure (PNNL Building America). The ADC flex duct standard: supports every 4 ft or closer, no more than 1/2 in of sag per foot, so about 2 in at the middle of a 4 ft span. DuctWise's Check tab says a 6 in flex at 80 CFM is the right size, but that's pulled tight, not hanging. What's the longest strap span you've found in an attic? Link in bio: DuctWise HVAC Duct Calculator #hvac #hvactech #flexduct #ductwork #hvaclife