Let’s look at a typical spring/diaphragm pneumatic actuator connected to a flow control valve in…
Let’s look at a typical spring/diaphragm pneumatic actuator connected to a flow control valve in action.
1️⃣ The PLC analog output card produces a 4 to 20 mA current to move the actuator from fully open to fully closed.
2️⃣ A signal conditioner called a current-to-pressure (I/P) transducer converts the 4 to 20 mA signal into a 3 to 15 psi pneumatic signal.
3️⃣ This pneumatic signal is sent to the actuator, causing it to move and adjust the position of a valve.
⭐ In many processes, a valve positioner is required. In a nutshell, a positioner receives the control signal and provides the necessary additional air pressure to move the valve to its required position.